The Schneider Electric A9D42613 is an Acti9 iDPN Vigi RCBO — a combined overcurrent and earth-leakage protection device in a single 1P+N module. The thermal-magnetic trip unit provides overcurrent protection with a C-curve (magnetic tripping between 5 and 10 times In), and the integrated earth-leakage element trips at 300 mA sensitivity. Breaking capacity is 6000 A Icn at 230...240 V AC, 50 Hz, compliant with EN/IEC 61009-2-1.
Clip-on mounting on a DIN rail, 36 mm wide (4 x 9 mm pitches). The connection pitch between phase and neutral is 9 mm. Terminals accept 1...16 mm² rigid or 1...10 mm² flexible wire; strip length 15 mm, tightening torque 2 N.m. IP20 on the front, IP40 inside the modular enclosure. Rated for 95 % relative humidity at 55 °C, tropicalisation class 2 per IEC 60068-1.