It protects a 1P+N circuit at 25 A rated current, C-curve magnetic trip (5–10 x In), with integrated 300 mA earth-leakage protection. Clip-on mounting to DIN rail, 4 module pitches wide, with a 9 mm phase-to-neutral pitch. That means it handles the damp, dusty environment of an outdoor-rated panel without derating.
The 300 mA sensitivity is for earth-leakage protection against fire risk, not personal shock protection (that would be 30 mA). It suits submain or final-circuit distribution where the upstream RCD is already 30 mA. Thermal-magnetic trip technology, no electronics to fail in the overcurrent path.
Integration notes
Single terminal top or bottom accepts 1–16 mm² rigid, 1–10 mm² flexible. Neutral on the left, phase on the right — standard for Acti9 boards. Local signalling shows ON, OFF, and fault trip status through the toggle window. IP20 on the body, IP40 inside the modular enclosure.