Rated 32 A with a C-curve magnetic trip (5–10 × In) and 6 kA breaking capacity at 230–240 V AC, 50 Hz, per EN/IEC 61009-2-1. Integrated 300 mA earth-leakage protection covers one protected pole plus switched neutral, left-side neutral position.
Single terminal top or bottom accepts 1–16 mm² rigid or 1–10 mm² flexible; tightening torque 2 N·m, strip length 15 mm. IP20 enclosure, IP40 within modular enclosure. Local signalling shows ON, OFF, and fault trip states.