Schneider Electric A9D47220 — Residual Current Breakers (RCCB/RCBO)

A9D47220 Acti9 iC60 RCBO, 20 A, 30 mA, Curve B, 2P

MPNA9D47220
Obsolete

Schneider Electric Acti9 iC60 RCBO, 2P, 20 A rated current, 30 mA earth-leakage sensitivity, curve B, 10 kA Icn, clip-on DIN rail mount, white.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D47220 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D47220 — Electrical Ratings
ParameterValue
Rated current (In)20 A
Rated operational voltage (Ue)220...240 V AC 50 Hz
Poles description2P
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D47220 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60 RCBO
A9D47220 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule
Wire stripping length12 mm for top or bottom connection
Terminal tightening torque2 N.m
Width36 mm
Height86 mm
Depth78 mm
A9D47220 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
IP degree of protectionIP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529
Relative humidity95 % at 55 °C
Tropicalisation2
A9D47220 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 61009-2-1

Product details

What this RCBO delivers

The Schneider Electric A9D47220 is a 2-pole Acti9 iC60 RCBO — a combined overcurrent and residual-current device rated for 20 A with 30 mA earth-leakage sensitivity. Curve B magnetic tripping (3...5 x In) suits circuits with low inrush, like lighting or general socket outlets. The 10 kA Icn breaking capacity at 220...240 V AC (15 kA Icu per EN/IEC 60947-2) covers most distribution boards in residential or light commercial builds. Thermal-magnetic trip unit, no electronics to fail on the overcurrent side. IP40 in a distribution enclosure, IP20 bare. Toggle control with local ON/OFF/fault trip indication.

Limitation class 3 per the latter standard. Carries quality marks NF, KEMA-KEUR, IMQ, VDE. Overvoltage category III per IEC 60364. Tropicalisation class 2 for humid environments — 95 % RH at 55 °C.

Frequently asked questions

Where can I buy A9D47220 and what is the lead time?

Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for the latest lead time and price.

What is A9D47220's listed depth?

The depth is 78 mm.

What is A9D47220's listed range?

It belongs to the Acti9 range, specifically the iC60 RCBO family.

What compliance documentation does this brand provide for A9D47220?

The part carries quality labels NF, KEMA-KEUR, IMQ, and VDE, and is built to EN/IEC 60947-2 and EN/IEC 61009-2-1. Overvoltage category III per IEC 60364. RoHS/REACH/UL documentation is typically available from the manufacturer upon request.

MPN