Specifications

A9D47225 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D47225 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)220...240 V AC 50 Hz
Poles description2P
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D47225 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60 RCBO
A9D47225 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule
Wire stripping length12 mm for top or bottom connection
Terminal tightening torque2 N.m
Width36 mm
Height86 mm
Depth78 mm
A9D47225 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
IP degree of protectionIP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529
Relative humidity95 % at 55 °C
Tropicalisation2
A9D47225 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 61009-2-1

Product details

The Schneider Electric A9D47225 is an Acti9 iC60 RCBO — a combined miniature circuit breaker and residual-current device in one 36 mm-wide, 2-pole module that clips onto a DIN rail. It protects a single-phase outgoer against overload, short-circuit (B curve, magnetic trip 3–5 x In), and earth leakage (30 mA sensitivity) in one unit. The thermal-magnetic trip unit gives you the standard MCB response plus integrated RCD protection, saving a DIN position versus separate breaker and RCCB.

Rated 25 A (In) with a breaking capacity of 10 kA Icn at 220–240 V AC (15 kA Icu per IEC 60947-2). The 15 kA Icu (ultimate breaking capacity per IEC 60947-2) is higher but is a one-shot rating; the breaker may need replacement after that fault. For most distribution boards with a typical upstream fuse or MCCB, 10 kA Icn is adequate for residential and light commercial outgoers. This RCBO covers both phase and neutral (2 poles protected, 2P device), so it disconnects both lines on a fault.

Tightening torque 2 N·m. IP40 in a distribution enclosure, IP20 bare — fine for enclosed panels, not for washdown areas.

Frequently asked questions

What is the breaking capacity of A9D47225?

10 kA Icn at 220–240 V AC per EN/IEC 61009-2-1, and 15 kA Icu per IEC 60947-2.