It combines a 25 A thermal-magnetic circuit breaker (D curve) with a 30 mA earth-leakage module in a single 18 mm wide, clip-on DIN-rail housing. Rated 25 A at 50 °C with a 10 kA breaking capacity (Icn at 230/240 V AC, 50/60 Hz), it protects final circuits against overload, short-circuit, and earth faults in TN earthing systems. The integrated 30 mA earth-leakage protection (sensitivity per IEC 61009-1) covers personnel and fire risk in one device, saving a DIN rail position versus separate MCB + RCCD.
Clip-on mounting to a 45 mm grid DIN rail. Neutral is on the left; the toggle actuator provides local ON/OFF indication and accepts a Ø 4 mm padlock for lockout/tagout. Screw-clamp terminals: top accepts 1–25 mm² rigid or 1–16 mm² flexible; bottom accepts 1–16 mm² rigid or 1–10 mm² flexible. Strip lengths are 14 mm (top) and 13 mm (bottom).
Certified to BS EN 61009-1, IEC 61009-1, IEC 61009-2-2, and AS/NZS 61009.1 — the governing standards for RCBOs. Suitable for isolation per the manufacturer's declaration. Electrical endurance rated at 5000 cycles; mechanical endurance at 20000 cycles. Surge current withstand is 250 A.