The Schneider Electric A9D52613 is an Acti9 iDPN Vigi residual-current circuit breaker with overcurrent protection (RCBO) — one module wide, combining a 13 A thermal-magnetic MCB and a 100 mA earth-leakage trip in a single 1P+N package.
Rated 13 A at 230...240 V AC, 50 Hz, with a breaking capacity of 6000 A Icn per EN/IEC 61009-2-1. The 100 mA earth-leakage sensitivity (AC type, integrated) protects against insulation faults and indirect contact, not direct human touch (that would need 30 mA). It is sized for distribution outgoers feeding fixed equipment, socket circuits, or sub-distribution where a 30 mA RCD would nuisance-trip on leakage from permanently connected loads. Thermal-magnetic trip technology means the thermal bimetal handles overloads (slow response, inverse-time) and the solenoid handles short-circuits (instantaneous above the C-curve threshold).
Connection pitch is 9 mm between phase and neutral, matching the standard Acti9 comb-busbar pitch.