Skip to main content
Schneider Electric A9D52625 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D52625 Acti9 iDPN Vigi RCBO, 25 A, C-cu

MPNA9D52625
Active

Schneider Electric Acti9 iDPN Vigi RCBO, 1P+N, 25 A, C-curve, 100 mA earth-leakage sensitivity, 6000 A Icn, clip-on DIN rail, white.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9D52625 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)100 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D52625 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)230...240 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D52625 — Identification
ParameterValue
Product nameActi9 iDPN Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiDPN N Vigi
A9D52625 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsSingle terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule
Wire stripping length15 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height85 mm
Depth73 mm
A9D52625 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9D52625 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

Rated 25 A with a C-curve magnetic trip (5...10 x In) and 100 mA residual-current sensitivity, it breaks up to 6000 A Icn at 230...240 V AC, 50 Hz, per EN/IEC 61009-2-1. The thermal-magnetic trip unit handles both overload and short-circuit; the integrated earth-leakage element covers ground faults. This is the outgoer protection for final subcircuits in distribution boards.

The 25 A rated current and C-curve mean this RCBO is sized for general-purpose socket-outlet circuits and small inductive loads — lighting, small motors, control transformers — where inrush can reach 5–10 times the rated current without nuisance tripping. The 100 mA earth-leakage threshold is higher than the 30 mA used for personal shock protection; it suits circuits where some standing leakage is normal (long cable runs, industrial equipment with filters) and the goal is fire protection or equipment damage prevention rather than personnel safety.

Terminals accept 1...16 mm² rigid or 1...10 mm² flexible (with or without ferrule); strip length 15 mm, tighten to 2 N.m. IP20 on the front, IP40 inside the modular enclosure. The toggle gives local ON/OFF/fault-trip indication.

Frequently asked questions

What is the breaking capacity of A9D52625?

6000 A Icn at 230...240 V AC, 50 Hz, conforming to EN/IEC 61009-2-1.

What earth-leakage sensitivity does this RCBO have?

100 mA, integrated into the device.

Where can I buy A9D52625 and how is it quoted?

Sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN
A9D52625