What this RCBO does in the panel
The 6 kA Icn breaking capacity at 230...240 V AC, 50 Hz, conforms to EN/IEC 61009-2-1, covering the majority of residential and light-commercial distribution boards. Clip-on mounting on DIN rail, 36 mm wide, with the neutral on the left and a 9 mm phase-to-neutral pitch — standard for Acti9 enclosures.
Mounts on DIN rail via clip-on — no screws. Tightening torque 2 N.m top or bottom; strip length 15 mm. The 9 mm pitch between phase and neutral matches the Acti9 busbar system. IP20 on the device body, IP40 inside the modular enclosure.