The 32 A rated current (In) and B-curve magnetic trip (3 to 5 × In) mean it protects lighting and general-purpose socket circuits where inrush is moderate, not high-starting loads like motors. The 30 mA earth-leakage sensitivity provides personal protection against direct contact, and the 6 kA breaking capacity at 380–415 V AC (Icn per EN/IEC 61009-2-1) is sized for residential and light commercial distribution boards where the prospective fault current stays under that level.
Deployment context
The 18 mm phase-to-phase pitch and 9 mm phase-to-neutral pitch match the Acti9 modular grid.
Limitation class 3 (energy-limiting) per the same standard, meaning it restricts let-through energy in a fault. The IP40 modular enclosure rating (with IP20 at terminals) covers indoor panel use.