It carries a 16 A rated current (B-curve), integrated 30 mA earth-leakage protection, and a 6 kA breaking capacity at 230…240 V AC, 50 Hz, certified to EN/IEC 61009-2-1. The thermal-magnetic trip unit provides both overload and short-circuit protection; magnetic tripping occurs at 3…5 × In. This is a current-production part, actively manufactured by Schneider Electric.
The 30 mA sensitivity is the standard threshold for personal protection against indirect contact (earth faults) in final circuits per IEC 60364.
The 1P+N format has the neutral on the left, phase on the right. Terminals accept 1…16 mm² rigid or 1…10 mm² flexible (with or without ferrule); wire strip length is 15 mm. IP20 on the body, IP40 inside a modular enclosure. The toggle provides local indication of ON, OFF, and fault-trip states.