A9D61816 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9D61816 — Electrical Ratings
ParameterValue
Rated current (In)16 A at 50 °C
Rated operational voltage (Ue)230/240 V AC 50/60 Hz
Poles description1P + Ns
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D61816 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60N RCBO
A9D61816 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsScrew clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible
Wire stripping lengthPower circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection
Terminal tightening torquePower circuit: 3.5 N.m top Power circuit: 2 N.m bottom
Width18 mm
Height110 mm
Depth77.5 mm
A9D61816 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Relative humidity95 % at 55 °C
Tropicalisation2
A9D61816 — Approvals
ParameterValue
StandardsIEC 61009-2-2 IEC 61009-1 AS/NZS 61009.1

Product details

The Schneider Electric A9D61816 is an Acti9 iC60 RCBO — a residual current breaker with overcurrent protection, combining a 16 A thermal-magnetic MCB and a 30 mA earth-leakage module in a single 18 mm wide unit. Breaking capacity is 6 kA Icn at 230/240 V AC, 50/60 Hz — sufficient for most residential and light commercial distribution boards where the prospective fault current stays under that threshold.

Neutral is on the left, outgoing circuit on the right — standard for Acti9 single-pole RCBOs. Padlockable with a 4 mm diameter padlock for lockout/tagout. Toggle control with ON/OFF local signalling. Tightening torque: 3.5 N.m top, 2 N.m bottom.

Certified to IEC 61009-1 and IEC 61009-2-2 (RCBO product and EMC immunity standards), plus AS/NZS 61009.1 for Australian/New Zealand installations. Rated for TN earthing systems. Limitation class 3 — high energy-limiting performance for downstream equipment protection.

Frequently asked questions

Where can I buy A9D61816 and how do I get a price?

The A9D61816 is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is A9D61816's breaking capacity?

The A9D61816 has a breaking capacity of 6 kA Icn at 230/240 V AC, 50/60 Hz.

What earth-leakage sensitivity does A9D61816 provide?

The A9D61816 has an integrated earth-leakage protection with 30 mA sensitivity.

What compliance documentation does Schneider provide for A9D61816?

The A9D61816 is certified to IEC 61009-1, IEC 61009-2-2, and AS/NZS 61009.1. It is rated for TN earthing systems and carries limitation class 3 for energy limiting.