Skip to main content
Schneider Electric A9D61825 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D61825 Acti9 iC60 RCBO, 25 A, 30 mA, C-

MPNA9D61825
Active

Schneider Electric Acti9 iC60N RCBO, 1P + Ns, 25 A at 50 °C, 30 mA earth-leakage sensitivity, C-curve, 6000 A Icn at 230/240 V AC, clip-on DIN rail, white.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D61825 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9D61825 — Electrical Ratings
ParameterValue
Rated current (In)25 A at 50 °C
Rated operational voltage (Ue)230/240 V AC 50/60 Hz
Poles description1P + Ns
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D61825 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60N RCBO
A9D61825 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsScrew clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible
Wire stripping lengthPower circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection
Terminal tightening torquePower circuit: 3.5 N.m top Power circuit: 2 N.m bottom
Width18 mm
Height110 mm
Depth77.5 mm
A9D61825 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Relative humidity95 % at 55 °C
Tropicalisation2
A9D61825 — Approvals
ParameterValue
StandardsAS/NZS 61009.1 IEC 61009-2-2 IEC 61009-1

Product details

The Schneider Electric A9D61825 is an Acti9 iC60N RCBO — a residual current breaker with overcurrent protection, combining a 25 A thermal-magnetic MCB and a 30 mA earth-leakage module in one 18 mm wide unit.

Breaking capacity is 6000 A Icn at 230/240 V AC, 50/60 Hz. The 30 mA earth-leakage sensitivity covers personnel protection against indirect contact; combined with the TN earthing system this is the typical spec for a final subcircuit in a distribution board. The 25 A rating at 50 °C means you don't have to derate for a warm enclosure as long as ambient stays under that — common in a populated consumer unit or panel. Limitation class 3 means it lets through less energy than a class 1 or 2 device, so downstream equipment sees a smaller fault let-through — that matters for coordination with downstream SPDs or sensitive loads.

Mounting and wiring in the panel

Clip-on mount to DIN rail. Neutral on the left, which is the standard orientation for Acti9 RCBOs — make sure your busbar or pre-wired assembly respects that polarity. Strip 14 mm for the top connection, 13 mm for the bottom. IP20 finger-safe when installed in a closed panel. Padlockable with a 4 mm shackle for lockout/tagout.

Frequently asked questions

Where can I buy the A9D61825 and get a price?

The A9D61825 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is the A9D61825's breaking capacity?

The A9D61825 has a breaking capacity of 6000 A Icn at 230/240 V AC, 50/60 Hz. That's the standard fault level for domestic and light commercial IEC distribution boards.

What compliance documentation does this part carry?

The A9D61825 is certified to AS/NZS 61009.1, IEC 61009-2-2, and IEC 61009-1. These are the governing standards for RCBOs — residual current breakers with overcurrent protection — covering both the overcurrent and earth-leakage functions.

MPN