That means one device handles both overload/short-circuit and ground-fault detection in a distribution outgoer, saving a DIN slot versus separate MCB + RCCB.
Breaking capacity is 6 kA Icn at 380–415 V AC, 50 Hz, per EN/IEC 61009-2-1, and 6 kA Icu per EN/IEC 60947-2. The C-curve (magnetic trip 5–10 × In) means it holds through motor inrush and capacitive loads without nuisance tripping — typical for general-purpose circuits feeding pumps, fans, or small machines. The 30 mA earth-leakage sensitivity provides personnel protection per IEC 60364.
Clip-on mounting to DIN rail, 54 mm wide (6 × 9 mm pitches), 86 mm tall, 78 mm deep. Tunnel-type terminals accept 1–35 mm² rigid or 1–25 mm² flexible cable; strip length 12 mm, tighten to 2 N·m. Local signalling shows ON, OFF, and fault-trip status on the toggle.
Carries quality marks NF, KEMA-KEUR, VDE, IMQ. Overvoltage category III per IEC 60364. Limitation class 1 per EN/IEC 61009-2-1. Tropicalisation level 2. Electrical endurance 10,000 cycles, mechanical 20,000 cycles.