Rated 20 A with a C-curve magnetic trip (5 to 10 x In) and 30 mA earth-leakage sensitivity, it protects both against overloads/short-circuits and against ground faults in a single 54 mm wide module. The 6 kA breaking capacity (Icn/Icu at 380–415 V AC, 50 Hz) meets EN/IEC 60947-2 and EN/IEC 61009-2-1, so it safely interrupts fault currents up to that level without upstream cascading issues in a standard distribution board.
Clip-on mounting to DIN rail, 9 mm pole pitch, occupying 6 pitches (54 mm width). Tunnel terminals accept 1–35 mm² rigid or 1–25 mm² flexible conductors; strip length 12 mm, tighten to 2 N·m. IP40 in a distribution enclosure, IP20 otherwise. Local signalling shows ON, OFF, and fault trip status on the toggle.