Skip to main content
Schneider Electric A9D67320 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D67320 Acti9 iC60 RCBO, 20 A, 30 mA, 6

MPNA9D67320
Obsolete

Schneider Electric Acti9 iC60 RCBO, 3P, 20 A, C-curve, 30 mA, 6 kA, clip-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D67320 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D67320 — Electrical Ratings
ParameterValue
Rated current (In)20 A
Rated operational voltage (Ue)380...415 V AC 50 Hz
Poles description3P
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D67320 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60 RCBO
A9D67320 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules6
Terminal connectionsTunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule
Wire stripping length12 mm for top or bottom connection
Terminal tightening torque2 N.m
Width54 mm
Height86 mm
Depth78 mm
A9D67320 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
IP degree of protectionIP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529
Relative humidity95 % at 55 °C
Tropicalisation2
A9D67320 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 61009-2-1

Product details

Rated 20 A with a C-curve magnetic trip (5 to 10 x In) and 30 mA earth-leakage sensitivity, it protects both against overloads/short-circuits and against ground faults in a single 54 mm wide module. The 6 kA breaking capacity (Icn/Icu at 380–415 V AC, 50 Hz) meets EN/IEC 60947-2 and EN/IEC 61009-2-1, so it safely interrupts fault currents up to that level without upstream cascading issues in a standard distribution board.

Clip-on mounting to DIN rail, 9 mm pole pitch, occupying 6 pitches (54 mm width). Tunnel terminals accept 1–35 mm² rigid or 1–25 mm² flexible conductors; strip length 12 mm, tighten to 2 N·m. IP40 in a distribution enclosure, IP20 otherwise. Local signalling shows ON, OFF, and fault trip status on the toggle.

Frequently asked questions

What is A9D67320's breaking capacity?

6 kA Icn/Icu at 380–415 V AC, 50 Hz, conforming to EN/IEC 61009-2-1 and EN/IEC 60947-2.

What compliance documentation does this brand provide for A9D67320?

The part carries IMQ, VDE, KEMA-KEUR, and NF quality labels, and is rated for tropicalisation class 2 (95% RH at 55 °C). Standards compliance includes EN/IEC 60947-2 and EN/IEC 61009-2-1.

MPN
A9D67320