The Schneider Electric A9D67410 is an Acti9 iC60 RCBO — a combined overcurrent and earth-leakage protection device in a 4-pole, C-curve, 10 A, 30 mA configuration. The 4 protected poles cover a three-phase outgoer with neutral, which is what you want for a motor feeder or a distribution sub-feed where you need both short-circuit and ground-fault protection in one 72 mm wide package.
The 10 A rated current with a C-curve means the magnetic trip fires between 5 and 10 times In — so 50 to 100 A instantaneous. That's the standard choice for general-purpose distribution and moderate motor starting where you don't want nuisance trips from inrush. The 30 mA earth-leakage sensitivity meets the typical requirement for personnel protection in most IEC territories.
Lifecycle status is current — active catalogue part. The Acti9 family is Schneider's current-generation residential and commercial final-distribution range.
It also holds VDE, KEMA-KEUR, NF, and IMQ quality labels, which covers acceptance in most European and many export markets. Limitation class is 1 per EN/IEC 61009-2-1, meaning it limits let-through energy to a defined level — relevant for downstream device coordination.
Installation notes
Clip-on mounting onto a standard DIN rail.