Rated 13 A with a C curve (magnetic trip 5–10 x In) and 30 mA earth-leakage sensitivity, it handles both short-circuit and residual-current protection in one 72 mm wide unit. Breaking capacity is 6 kA Icn / Icu at 380–415 V AC 50 Hz, compliant with EN/IEC 61009-2-1 and EN/IEC 60947-2.
The 30 mA residual-current sensitivity covers personnel protection (30 mA is the standard threshold for shock protection per IEC 60364). 6 kA breaking capacity at 415 V is adequate for most commercial and light industrial distribution boards; verify the prospective fault current at the installation point — if it exceeds 6 kA, step up to a higher-rated device in the iC60 range. The 9 mm pole pitch keeps the 4P unit at 72 mm wide — 8 pitches of 9 mm. IP40 in the distribution enclosure, IP20 on the terminals; fine for enclosed panels, not for washdown zones.