Acti9 iC60 RCBO — 4P, C-curve, 25 A, 30 mA
Rated 25 A with a C-curve magnetic trip (5–10 x In) and 30 mA earth-leakage sensitivity, it clips onto a DIN rail and occupies 8 x 9 mm pitches (72 mm wide). The thermal-magnetic trip unit handles both overload and short-circuit protection; the integrated earth-leakage section covers personnel protection at 30 mA. Breaking capacity is 6 kA Icn / Icu at 380–415 V AC, 50 Hz, certified to EN/IEC 61009-2-1 and EN/IEC 60947-2. Overvoltage category III per IEC 60364 suits it for fixed-installation outgoers.
Clip-on mounting to a standard DIN rail. The 9 mm pole pitch matches standard Acti9 busbar and comb spacing — no adapters needed for multi-pole distribution blocks. IP40 in a distribution enclosure (IP20 bare) per IEC 60529.
Current production — no end-of-life notice. The A9D67425 carries VDE, NF, IMQ, and KEMA-KEUR quality labels, confirming type-test compliance for European and selected international markets. Rated for 10,000 electrical and 20,000 mechanical cycles. Local signalling shows ON, OFF, and fault-trip status on the toggle — no auxiliary contact needed for visual indication at the panel door.