It integrates earth-leakage detection at 30 mA sensitivity with thermal-magnetic overcurrent protection rated at 16 A, C-curve (magnetic trip 5–10 x In). The 6 kA breaking capacity (Icu per EN/IEC 60947-2, Icn per EN/IEC 61009-2-1 at 380–415 V AC) is sized for distribution sub-circuits in residential and commercial panels where the prospective fault current stays under that threshold.
Clip-on mounting on standard DIN rail (35 mm per EN 60715). Width is 72 mm (8 x 9 mm pitches) — occupies four module spaces in the enclosure. Depth 78 mm, height 86 mm. Connection pitch is 9 mm between poles. Wire stripping length 12 mm for top or bottom entry. IP40 in distribution enclosure, IP20 at the terminals per IEC 60529.
Listed as current-production (active lifecycle stage). Carries quality labels IMQ, KEMA-KEUR, NF, VDE. Overvoltage category III per IEC 60364. Tropicalisation class 2. Rated for 50 Hz AC networks only.
Durability and environmental limits
Mechanical durability rated at 20,000 cycles; electrical durability at 10,000 cycles. Surge current withstand 3000 A. Limitation class 1 per EN/IEC 61009-2-1. Local signalling shows ON, OFF, and fault trip status.