It carries a 20 A rated current on a C-curve trip characteristic and integrates 30 mA earth-leakage protection, so one device covers both the branch-circuit overcurrent and the personnel / equipment GFCI function on a three-phase outgoer. Breaking capacity is 6 kA Icu at 380…415 V AC 50 Hz per EN/IEC 60947-2, with an Icn of 6 kA per EN/IEC 61009-2-1. Clip-on mounting to DIN rail, 9 mm pole pitch, 72 mm wide × 86 mm high × 78 mm deep. IP40 in a distribution enclosure, IP20 on the terminals. The thermal-magnetic trip unit is field-proven in the Acti9 range; mechanical durability is 20,000 cycles, electrical 10,000 cycles.
Integration & wiring
Tunnel-type terminals top and bottom accept 1…35 mm² rigid, 1…25 mm² flexible, or 1…25 mm² flexible with ferrule. Tightening torque 2 N·m; strip length 12 mm. The 9 mm pole pitch matches standard Acti9 busbars and comb-bridge accessories. Local signalling shows ON, OFF, and fault-trip status via the toggle position. The device is intended as an outgoer in a distribution board — not a main incomer. The 30 mA earth-leakage threshold is the standard for personnel protection in most IEC-based installations.