Rated 32 A with a 30 mA earth-leakage sensitivity and a C-curve magnetic trip (5...10 x In), it clips onto a DIN rail and fits an 8-module pitch (72 mm wide).
The 6 kA breaking capacity (Icn at 380...415 V AC, 50 Hz, per EN/IEC 61009-2-1; Icu per EN/IEC 60947-2) is the standard fault-interruption rating for most commercial and light-industrial distribution boards in Europe. The 30 mA earth-leakage threshold provides personal protection against direct contact; it is the most common sensitivity for final circuits in residential and commercial panels. Limitation class 1 per EN/IEC 61009-2-1 means the RCBO limits let-through energy to a defined level under fault conditions, reducing stress on downstream wiring.
The 72 mm width (8 x 9 mm pitches) occupies four standard module positions. The connection pitch between poles is 9 mm. IP40 in a distribution enclosure (IP20 for the terminal area) per IEC 60529.