A9D87413 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D87413 — Electrical Ratings
ParameterValue
Rated current (In)13 A
Rated operational voltage (Ue)380...415 V AC 50 Hz
Poles description4P
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D87413 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60 RCBO
A9D87413 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules8
Terminal connectionsTunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule
Wire stripping length12 mm for top or bottom connection
Terminal tightening torque2 N.m
Width72 mm
Height86 mm
Depth78 mm
A9D87413 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
IP degree of protectionIP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529
Relative humidity95 % at 55 °C
Tropicalisation2
A9D87413 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 61009-2-1

Product details

It protects a 13 A final circuit against overload and short-circuit (curve B, magnetic trip 3 to 5 x In) and against earth faults at 30 mA sensitivity, all in a single 72 mm wide unit that clips onto a DIN rail. Rated breaking capacity is 6 kA Icn / Icu at 380–415 V AC, 50 Hz, per EN/IEC 61009-2-1 and EN/IEC 60947-2.

Clip-on mounting to DIN rail, 9 mm pole pitch, 8 pitches wide — the 72 mm width occupies four standard 18 mm module positions. Tunnel-type terminals accept 1 to 35 mm² rigid or 1 to 25 mm² flexible cable; strip length 12 mm, tighten to 2 N·m. IP40 in a distribution enclosure, IP20 bare.

Approvals and standards

Carries NF, IMQ, VDE, and KEMA-KEUR quality labels — accepted across European and many international installations. Complies with EN/IEC 60947-2 (MCB performance) and EN/IEC 61009-2-1 (RCBO specific), overvoltage category III per IEC 60364.