It protects a 13 A final circuit against overload and short-circuit (curve B, magnetic trip 3 to 5 x In) and against earth faults at 30 mA sensitivity, all in a single 72 mm wide unit that clips onto a DIN rail. Rated breaking capacity is 6 kA Icn / Icu at 380–415 V AC, 50 Hz, per EN/IEC 61009-2-1 and EN/IEC 60947-2.
Clip-on mounting to DIN rail, 9 mm pole pitch, 8 pitches wide — the 72 mm width occupies four standard 18 mm module positions. Tunnel-type terminals accept 1 to 35 mm² rigid or 1 to 25 mm² flexible cable; strip length 12 mm, tighten to 2 N·m. IP40 in a distribution enclosure, IP20 bare.
Approvals and standards
Carries NF, IMQ, VDE, and KEMA-KEUR quality labels — accepted across European and many international installations. Complies with EN/IEC 60947-2 (MCB performance) and EN/IEC 61009-2-1 (RCBO specific), overvoltage category III per IEC 60364.