Skip to main content
Schneider Electric A9D97410

Schneider Electric A9D97410 Acti9 iC60 RCBO, 4P, 10 A, 30 mA

MPN A9D97410
Obsolete

Schneider Electric Acti9 iC60 RCBO, 4P, 10 A rated, 30 mA earth leakage, B-curve, 6 kA breaking capacity, clip-on DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9D97410 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Voltage380...415 V AC 50 Hz
Insulation voltage ui500 V AC 50 Hz
Breaking capacity6000 A Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 6 kA Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2
Terminal pitch9 mm between poles
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...70 °C
ColorWhite

All specifications

A9D97410 additional specifications
ParameterValue
Depth78 mm
Width72 mm
Height86 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...60 °C

Product details

The Schneider Electric A9D97410 is an Acti9 iC60 RCBO — a combined residual-current circuit breaker with overcurrent protection, in a 4-pole (4P) configuration. Rated 10 A with 30 mA earth-leakage sensitivity and a B-curve magnetic trip (3–5 x In), it's built for final-circuit protection in distribution boards where both overload/short-circuit and earth-fault protection are needed in one DIN-rail module.

The 30 mA earth-leakage threshold provides personnel protection (per IEC 61009-2-1) and is the standard sensitivity for socket-outlet circuits in most domestic and commercial installations. The limitation class 1 (per EN/IEC 61009-2-1) means it lets through a defined let-through energy; coordination with upstream devices should follow the manufacturer's selectivity tables.

Clip-on mounting to DIN rail, 9 mm pole pitch, occupying 8 pitches (72 mm width). IP40 in a distribution enclosure, IP20 at the terminals — fine for a clean panel, not for washdown areas.

MPN