Rated 13 A with a B-curve magnetic trip (3–5 × In) and 30 mA earth-leakage sensitivity, it delivers 6 kA breaking capacity at 380–415 V AC, 50 Hz, per EN/IEC 61009-2-1 and EN/IEC 60947-2. The thermal-magnetic trip unit handles both overload and short-circuit protection, while the integrated earth-leakage block covers ground faults.
The 13 A rated current (In) sets the continuous load the RCBO can carry without tripping — sized for a branch circuit drawing up to 13 A, typical for lighting or small power outlets in distribution boards. The 30 mA earth-leakage sensitivity provides personal protection against indirect contact (touch voltage) per IEC 60364, making it appropriate for final circuits in residential or commercial outgoer positions.
Integration and installation
Clip-on mounting on DIN rail (EN 60715) with a 9 mm pole pitch — occupies 4 modules (36 mm) in the distribution board. IP40 in distribution enclosure, IP20 on the terminals. Tunnel terminals: tighten to 2 N·m, strip 12 mm. Wire range: 1–35 mm² rigid, 1–25 mm² flexible (with or without ferrule). The toggle provides local signalling for ON, OFF, and fault trip. Tropicalisation class 2 covers high-humidity environments (95% RH at 55 °C).