It carries a 16 A rated current (In) with a B tripping curve (magnetic release at 3 to 5 times In), and integrated 30 mA earth-leakage protection. The breaking capacity is 6 kA Icu at 380–415 V AC 50 Hz per EN/IEC 60947-2, and 6 kA Icn per EN/IEC 61009-2-1. This is a thermal-magnetic trip unit, so it responds to both sustained overloads (thermal bimetal) and short-circuit faults (magnetic solenoid). The 30 mA residual-current element covers personnel protection against earth faults — the sensitivity level required for socket-outlet circuits in most residential and commercial installations. The RCBO mounts via clip-on onto a DIN rail, occupying 8 modules of 9 mm pitch.
It holds quality marks from IMQ, VDE, NF, and KEMA-KEUR. The IP rating is IP40 in a distribution enclosure, IP20 for the device body. Overvoltage category III per IEC 60364. The limitation class is 1 conforming to EN/IEC 61009-2-1, meaning it limits let-through energy to a level that protects downstream equipment within its rated breaking capacity.