Skip to main content
Schneider Electric A9D97425 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D97425 Acti9 iC60 RCBO, 25 A, 30 mA, B-

MPNA9D97425
Obsolete

Schneider Electric Acti9 iC60 RCBO, A9D97425, 4P, 25 A rated, 30 mA earth leakage, B-curve, 6 kA Icu, clip-on DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9D97425 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D97425 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)380...415 V AC 50 Hz
Poles description4P
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D97425 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60 RCBO
A9D97425 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules8
Terminal connectionsTunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule
Wire stripping length12 mm for top or bottom connection
Terminal tightening torque2 N.m
Width72 mm
Height86 mm
Depth78 mm
A9D97425 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
IP degree of protectionIP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529
Relative humidity95 % at 55 °C
Tropicalisation2
A9D97425 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 61009-2-1

Product details

The A9D97425 is a Schneider Electric Acti9 iC60 RCBO — a combined residual-current circuit breaker with overcurrent protection, in a 4-pole (4P) configuration. It carries a 25 A rated current (In) with a B-curve magnetic trip threshold of 3...5 x In, meaning it trips instantaneously on short-circuit currents between 75 A and 125 A — suited for protecting general-purpose circuits with moderate inrush, like lighting or socket outlets. The integrated earth-leakage protection is set to 30 mA sensitivity, covering personnel protection (additional shock-risk mitigation) per IEC standards. Breaking capacity is 6 kA Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2, and 6 kA Icn per EN/IEC 61009-2-1 — adequate for most distribution outgoing circuits in residential and light commercial panels.

Clip-on mounting to DIN rail (EN/IEC 60715) — 9 mm pole pitch, 8 pitches wide (72 mm width, 86 mm height, 78 mm depth). IP40 in distribution enclosure, IP20 on the terminals. Toggle control with local ON/OFF/fault-trip indication. Fits standard Acti9 distribution boards and enclosures.

Frequently asked questions

Where can I buy A9D97425 and what is the lead time?

The A9D97425 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings of A9D97425?

25 A rated current, 30 mA earth-leakage sensitivity, B-curve (3...5 x In magnetic trip), 6 kA Icu breaking capacity at 380...415 V AC, 4 poles.

What compliance documentation does Schneider provide for A9D97425?

The part carries IMQ, KEMA-KEUR, VDE, and NF quality labels, and conforms to EN/IEC 60947-2 and EN/IEC 61009-2-1. Standard RoHS/REACH documentation is available from Schneider Electric.

MPN