Skip to main content
Schneider Electric A9DC2932 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9DC2932 Acti9 iC60H3 RCBO, 32 A, 10 kA,

MPNA9DC2932
Active

Schneider Electric Acti9 iC60H3 RCBO, 3P + Ns, 32 A rated, Curve C, 10 kA breaking capacity at 400/415 V, 100 mA earth-leakage sensitivity, DIN-rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9DC2932 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)100 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9DC2932 — Electrical Ratings
ParameterValue
Rated current (In)32 A at 30 °C
Rated operational voltage (Ue)400/415 V
Poles description3P + Ns
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9DC2932 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60H3 RCBO
A9DC2932 — Mechanical
ParameterValue
Mounting supportDIN rail Chassis
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules6
Terminal connectionsScrew clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible
Wire stripping lengthPower circuit: 11 mm for bottom connection Power circuit: 14 mm for top connection
Terminal tightening torquePower circuit: 2.5 N.m top Power circuit: 2.5 N.m bottom
Width54 mm
Height112 mm
Depth77.2 mm
A9DC2932 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-25...70 °C
IP degree of protectionIP20
Relative humidity95 % at 55 °C
Tropicalisation2
A9DC2932 — Approvals
ParameterValue
StandardsAS/NZS 61009.1 IEC 61009-1 IEC 61009-2-2

Product details

The Schneider Electric A9DC2932 is an Acti9 iC60H3 RCBO — a residual current breaker with overcurrent protection, combining a 32 A thermal-magnetic MCB (Curve C) and a 100 mA earth-leakage module in one 54 mm-wide unit. It protects a 3P + Ns outgoing circuit against overload, short-circuit, and ground faults, with a 10 kA breaking capacity at 400/415 V AC per IEC 61009-1.

The 100 mA earth-leakage sensitivity is a higher threshold than the typical 30 mA for personal protection; it suits circuits where nuisance tripping from leakage is a concern, such as fixed equipment with inherent leakage.

Clip-on mounting to a DIN rail or chassis, 6 module pitches (54 mm wide), with screw-clamp terminals accepting 1…25 mm² rigid or 1…16 mm² flexible cable.

Frequently asked questions

What is the A9DC2932 used for?

It is a combined residual current breaker and overcurrent protection device (RCBO) for a 3P + Ns outgoing circuit. It protects against overload, short-circuit, and earth leakage in a single 54 mm-wide unit, typically in sub-distribution boards in TN earthing systems.

What is the breaking capacity of A9DC2932?

10,000 A Icn at 400/415 V AC, per IEC 61009-1.

Where can I buy A9DC2932?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
A9DC2932