Skip to main content
Schneider Electric A9DC6910 — Residual Current Breakers (RCCB/RCBO)

A9DC6910 Acti9 iC60 RCBO, 10 A, C-curve, 30 mA, 6 kA

MPNA9DC6910
Active

Schneider Electric Acti9 iC60 RCBO, A9DC6910, 3P + Ns, 10 A rated current, C-curve, 30 mA earth-leakage sensitivity, 6000 A Icn at 400/415 V, clip-on DIN-rail mount, IP20.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Residual Current Protection

A9DC6910 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication

Electrical Ratings

A9DC6910 — Electrical Ratings
ParameterValue
Rated current (In)10 A at 30 °C
Rated operational voltage (Ue)400/415 V
Poles description3P + Ns
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles

Identification

A9DC6910 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60N3 RCBO

Mechanical

A9DC6910 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules6
Terminal connectionsScrew clamp terminal (top) 1...25 mm² rigid without cable end
Wire stripping lengthPower circuit: 11 mm for bottom connection
Terminal tightening torquePower circuit: 2.5 N.m top
Width54 mm
Height112 mm
Depth77.2 mm

Environmental

A9DC6910 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-25...70 °C
IP degree of protectionIP20
Relative humidity95 % at 55 °C
Tropicalisation2

Approvals

A9DC6910 — Approvals
ParameterValue
StandardsAS/NZS 61009.1

Product details

It combines a 10 A thermal-magnetic circuit breaker (C-curve) with integrated 30 mA earth-leakage protection in a single 54 mm wide module that clips onto a DIN rail.

The 10 A rated current (at 30 °C) and C-curve trip characteristic make this RCBO suited for general-purpose circuits with moderate inrush — lighting banks, small motor loads, or socket outlets where the starting surge is higher than a B-curve would tolerate. The 30 mA earth-leakage sensitivity provides personal protection against indirect contact, complying with AS/NZS 61009.1. The 6000 A Icn at 400/415 V is the short-circuit breaking capacity under standard conditions; limitation class 3 means it limits let-through energy during a fault, reducing stress on downstream wiring. The device occupies 6 x 9 mm pitches (54 mm) on a DIN rail, with a depth of 77.2 mm and height of 112 mm. The screw-clamp terminals accept 1 to 25 mm² rigid cable; strip length is 11 mm for the bottom connection and tighten to 2.5 N.m.

Frequently asked questions

Where can I buy A9DC6910?

The A9DC6910 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of A9DC6910?

The breaking capacity is 6000 A Icn at 400/415 V AC, with limitation class 3.

What earth-leakage sensitivity does A9DC6910 provide?

The integrated earth-leakage protection is rated at 30 mA sensitivity.

What compliance standards does A9DC6910 meet?

It complies with AS/NZS 61009.1 for residual current breakers with overcurrent protection.

MPN