Skip to main content
Schneider Electric A9DC6940 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9DC6940 Acti9 iC60 RCBO, 40A, 30mA, 6kA

MPNA9DC6940
Active

Schneider Electric Acti9 iC60 RCBO, A9DC6940, 3P+N, 40 A, 30 mA earth leakage, 6000 A Icn at 400/415 V, C curve, clip-on DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Residual Current Protection

A9DC6940 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication

Electrical Ratings

A9DC6940 — Electrical Ratings
ParameterValue
Rated current (In)40 A at 30 °C
Rated operational voltage (Ue)400/415 V
Poles description3P + Ns
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles

Identification

A9DC6940 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60N3 RCBO

Mechanical

A9DC6940 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules6
Terminal connectionsScrew clamp terminal (top) 1...25 mm² rigid without cable end
Wire stripping lengthPower circuit: 11 mm for bottom connection
Terminal tightening torquePower circuit: 2.5 N.m top
Width54 mm
Height112 mm
Depth77.2 mm

Environmental

A9DC6940 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-25...70 °C
IP degree of protectionIP20
Relative humidity95 % at 55 °C
Tropicalisation2

Approvals

A9DC6940 — Approvals
ParameterValue
StandardsAS/NZS 61009.1

Product details

It protects a 3P+N outgoing circuit at 40 A (rated at 30 °C) with integrated 30 mA earth-leakage detection, so you get overcurrent and ground-fault protection from a single device that clips onto a DIN rail.

Rated 6000 A Icn at 400/415 V AC — that's the short-circuit breaking capacity per AS/NZS 61009.1. In a typical TN earthing system, this RCBO sits at the outgoer position, downstream of a higher-rated main breaker.

Thermal-magnetic trip and durability

The trip unit is thermal-magnetic — a bimetal strip handles overloads (slow, heat-dependent) and a solenoid handles short-circuits (instantaneous). Expect 5000 electrical cycles and 20000 mechanical cycles; that's a solid service life for a panel that isn't switched daily.

Clip-on DIN rail mount, 54 mm wide (6 x 9 mm pitches). Neutral on the left, 3 protected poles on the right. Screw-clamp terminals accept 1 to 25 mm² rigid cable; strip 11 mm for the bottom connection, torque to 2.5 N.m on the top power circuit. IP20 rated — fine inside an enclosed panel, not for wet environments. Padlockable with a 4 mm hasp for lockout/tagout.

Frequently asked questions

Where can I buy the A9DC6940 and get a price?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What is the A9DC6940's breaking capacity?

6000 A Icn at 400/415 V AC, per AS/NZS 61009.1.

What does the C curve mean on this RCBO?

The C curve trips magnetically between 5 and 10 times rated current (200–400 A for this 40 A unit), which suits moderate inrush from small motors or lighting without nuisance trips.

MPN