What this RCBO carries
Rated 32 A with a C-curve (magnetic trip 5–10 x In) and 10 kA breaking capacity at 230 V AC, it integrates both thermal-magnetic overcurrent protection and 300 mA earth-leakage detection in a single 36 mm wide module. The 10 kA Icn at 230 V AC meets EN/IEC 61009-2-1 for an RCBO in distribution outgoer positions.
Tunnel terminals top and bottom accept 1–16 mm² rigid or 1–10 mm² flexible; strip 14 mm, torque to 2 N.m. IP20 on the body, IP40 inside a modular enclosure — standard for distribution boards.