Skip to main content
Schneider Electric A9DCA610 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9DCA610 Acti9 iCV40 RCBO, 10 A, 30 mA, C

MPNA9DCA610
Active

Schneider Electric Acti9 iCV40 RCBO, A9DCA610, 1P+N, 10 A rated, C-curve, 30 mA earth leakage, 6 kA breaking capacity, DIN rail clip-on.

$272.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9DCA610 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)10 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication Fault indication
A9DCA610 — Electrical Ratings
ParameterValue
Rated current (In)10 A
Rated operational voltage (Ue)230 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles
A9DCA610 — Identification
ParameterValue
Product nameActi9 iCV40
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiCV40N
A9DCA610 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height94 mm
Depth74 mm
A9DCA610 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Operating altitude2000 m
A9DCA610 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The Schneider Electric A9DCA610 is an Acti9 iCV40 RCBO — a combined overcurrent and earth-leakage protective device for final circuits. It integrates a thermal-magnetic trip unit for overload and short-circuit protection with a 30 mA residual-current element, all in a single 36 mm wide module that clips onto a DIN rail. Rated 10 A with a C-curve magnetic trip (5 to 10 × In), it is sized for general-purpose socket outlets and lighting circuits where moderate inrush is expected. The 6 kA breaking capacity at 230 V AC (Icn per EN/IEC 61009-2-1) covers most residential and light commercial distribution boards. The integrated 30 mA earth-leakage protection meets the standard for personal protection against indirect contact in TN and TT systems.

Clip-on mounting to a DIN rail, 36 mm width (4 × 9 mm pitches). Neutral is on the left, phase on the right — standard for the Acti9 range. Tunnel terminals accept up to 16 mm² rigid or 10 mm² flexible cable; strip length 14 mm, torque to 2 N·m.

Frequently asked questions

What is the A9DCA610's rated current and earth-leakage sensitivity?

The A9DCA610 is rated 10 A with a 30 mA earth-leakage sensitivity. The magnetic trip is C-curve (5 to 10 × In). Breaking capacity is 6 kA at 230 V AC.

What standards does the A9DCA610 comply with?

It complies with EN/IEC 61009-2-1 for RCBOs. It also carries EAC and VDE quality labels. Overvoltage category III per IEC 60364, pollution degree 3.

Where can I buy the A9DCA610?

The A9DCA610 is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm current availability and pricing.

MPN
A9DCA610