Rated 16 A (In), C-curve, 1P+N, with a 6000 A Icn breaking capacity at 230 V AC per EN/IEC 61009-2-1. The integrated earth-leakage trips at 10 mA sensitivity, so it protects against both overload/short-circuit and ground faults in one DIN-rail module.
The 10 mA earth-leakage threshold is sensitive enough for circuits supplying wet areas or handheld equipment, but may nuisance-trip on long cable runs with leakage capacitance; verify the downstream load's leakage profile before committing the BOM line. Combined with the C-curve magnetic trip (5–10 × In), it coordinates well with upstream MCBs in a selective scheme — the RCBO clears the fault before the main breaker sees it. Clip-on DIN-rail mounting, 4 modules wide at 9 mm pitch, so it occupies 36 mm of rail space. IP20 body, IP40 inside an enclosure — standard for panel-mount distribution gear.