Schneider Electric A9DE2632 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9DE2632 Acti9 iCV40 RCBO, 32 A, 30 mA, C

MPNA9DE2632
Active

Schneider Electric Acti9 iCV40 RCBO, A9DE2632, 1P+N, 32 A rated current, 30 mA earth leakage, C-curve, 4.5 kA breaking capacity, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9DE2632 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication Fault indication
A9DE2632 — Electrical Ratings
ParameterValue
Rated current (In)32 A
Rated operational voltage (Ue)230 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9DE2632 — Identification
ParameterValue
Product nameActi9 iCV40
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiCV40
A9DE2632 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height85 mm
Depth73 mm
A9DE2632 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Operating altitude2000 m
A9DE2632 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The Schneider Electric A9DE2632 is an Acti9 iCV40 residual current circuit breaker with overcurrent protection (RCBO) — a single module that combines a 32 A thermal-magnetic MCB with a 30 mA earth leakage trip in one 1P+N package.

Rated breaking capacity is 4500 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1. That's the standard domestic and light commercial fault level for a final subcircuit in most European installations. Limitation class 3 per the same standard means it restricts let-through energy enough to allow basic selectivity with an upstream 63 A or 80 A S-curve MCB — useful when you're coordinating a distribution board without oversizing the main breaker.

Clip-on DIN rail mount, neutral on the left. Tunnel terminals top and bottom accept 1 to 16 mm² rigid or 1 to 10 mm² flexible cable; strip 14 mm and torque to 2 N·m. The device is IP20 (finger-safe) with the modular enclosure rated IP40 inside the panel.

Frequently asked questions

Where can I buy the A9DE2632 and get a price?

The A9DE2632 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the A9DE2632's breaking capacity?

The A9DE2632 has a breaking capacity of 4500 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1. That's the standard fault level for final subcircuits in domestic and light commercial installations.

What compliance documentation does Schneider provide for the A9DE2632?

The A9DE2632 carries VDE and IMQ quality labels and conforms to EN/IEC 61009-2-1. It is rated pollution degree 3 and overvoltage category III per IEC 60364. For specific RoHS/REACH/UL declarations, request the manufacturer's compliance documentation at quote time.

MPN