Rated 40 A with a C-curve magnetic trip (5 to 10 x In), it clears faults up to 6 kA at 400 V AC per EN/IEC 61009-2-1. The integrated 30 mA earth-leakage sensitivity catches ground faults before they become shock hazards, making this unit a fit for final subcircuits where both overcurrent and residual current protection are required in a single device.
The C-curve (5–10 x In) means magnetic tripping occurs between 200 A and 400 A for a 40 A unit — suited for loads with moderate inrush like small motor circuits or lighting banks, but not for high-inrush transformers or drives.
The 18 mm phase-to-phase and 9 mm phase-to-neutral pitch matches the standard Acti9 modular spacing. Tunnel terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible cable; torque to 2 N·m.