The A9DF7606 is a Schneider Electric Acti9 iCV40 RCBO — a single-module (1P+N) residual current breaker with overcurrent protection, rated 6 A, C-curve, 6 kA breaking capacity at 230 V AC, 50/60 Hz per EN/IEC 61009-2-1.
Installation and panel integration
Clip-on DIN-rail mount, 36 mm wide (4 x 9 mm pitches). Neutral is on the left side. Tunnel terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible cable; strip to 14 mm and torque to 2 N·m at top or bottom. Pollution degree 3, overvoltage category III — rated for fixed installation in a distribution board where transient overvoltages are controlled by upstream SPDs.
Selection note
This is a 1P+N RCBO — it switches the phase and monitors neutral for leakage, but does not provide overcurrent protection on the neutral. Rated earth-leakage sensitivity is 300 mA.