Skip to main content
Schneider Electric A9DF7625 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9DF7625 Acti9 iCV40 25A RCBO, 6000A, C-C

MPNA9DF7625
Active

Schneider Electric Acti9 iCV40 RCBO, A9DF7625, 25 A rated, C-curve, 6000 A breaking capacity, 300 mA earth-leakage, 1P+N, DIN-rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9DF7625 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationFault indication ON/OFF indication
A9DF7625 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)230 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles
A9DF7625 — Identification
ParameterValue
Product nameActi9 iCV40
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiCV40N
A9DF7625 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height85 mm
Depth73 mm
A9DF7625 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Operating altitude2000 m
A9DF7625 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The integrated earth-leakage protection trips at 300 mA, covering the whole outgoing circuit against ground faults.

Clip-on mounting to a standard DIN rail. The 36 mm width and 85 mm height match the Acti9 modular enclosure footprint. 4 x 9 mm pitches for the phase-to-neutral connection. Neutral is on the left. Tunnel terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible; tighten to 2 N·m. Wire stripping length 14 mm. IP20 body, IP40 in a modular enclosure — fine for a clean indoor distribution board, not for washdown areas.

Frequently asked questions

What is the breaking capacity of A9DF7625?

6000 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1. That is the rated short-circuit capacity for this RCBO.

What earth-leakage sensitivity does A9DF7625 have?

Integrated earth-leakage protection with 300 mA sensitivity. Suitable for general-purpose ground-fault protection on outgoing circuits.

What standards does A9DF7625 comply with?

Compliant with EN/IEC 61009-2-1, the RCBO product standard. Also carries VDE and EAC quality labels. Overvoltage category III per IEC 60364.

MPN
A9DF7625