Skip to main content
Schneider Electric A9DG3716 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9DG3716 Acti9 iCV40 RCBO, 16 A, 30 mA, B

MPNA9DG3716
Active

Schneider Electric Acti9 iCV40 RCBO, A9DG3716, 3P+N, 16 A, 30 mA, B curve, 6 kA, DIN rail.

$185.71Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9DG3716 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication Fault indication
A9DG3716 — Electrical Ratings
ParameterValue
Rated current (In)16 A
Rated operational voltage (Ue)400 V AC 50/60 Hz
Poles description3P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)440 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles
A9DG3716 — Identification
ParameterValue
Product nameActi9 iCV40
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiCV40N
A9DG3716 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules10
Terminal connectionsTunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width90 mm
Height93 mm
Depth73 mm
A9DG3716 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Operating altitude2000 m
A9DG3716 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

Rated 16 A with a 30 mA earth-leakage sensitivity and a B tripping curve, it protects branch circuits against both overload/short-circuit and ground faults.

For motor or transformer circuits with higher starting surges, a C or D curve would be needed to avoid nuisance tripping. The 30 mA residual sensitivity covers personnel protection (indirect contact) and fire prevention; it's the most common rating for final circuits in residential and commercial installations per IEC 60364. Thermal-magnetic trip technology means the thermal bimetal handles sustained overloads (time-inverse characteristic) while the solenoid reacts to high short-circuit currents. The limitation class 3 (EN/IEC 61009-2-1) indicates the device limits let-through energy well, reducing stress on downstream wiring and equipment during a fault. The 18 mm pole pitch keeps the 3P+N unit at a 4-module width (72 mm plus tolerance).

Frequently asked questions

What is the breaking capacity of A9DG3716?

The A9DG3716 has a rated breaking capacity of 6000 A Icn at 400 V AC 50/60 Hz, conforming to EN/IEC 61009-2-1. That means it can safely interrupt a fault current up to 6 kA at the rated voltage.

What compliance documentation does A9DG3716 carry?

The A9DG3716 is certified to EN/IEC 61009-2-1 and carries VDE and EAC quality labels. It is designed for overvoltage category III per IEC 60364 and pollution degree 3 environments.

Where can I buy A9DG3716?

The A9DG3716 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm offer.

MPN
A9DG3716