Rated 16 A with a B curve (magnetic trip 3–5 x In) and integrated 10 mA earth-leakage protection, it clears faults at 6 kA Icn per EN/IEC 61009-2-1. This is a 1P+N unit with neutral on the left, clip-on DIN rail mount, and IP20 finger-safe terminals.
The 10 mA sensitivity is the standout here — this is a high-sensitivity residual current trip, not the standard 30 mA. It's sized for circuits where even a small leakage to ground must be caught: wet environments, medical locations, or circuits supplying hand-held equipment where the extra protection is specified by code. The B curve (3–5 x In) means magnetic trip happens between 48 A and 80 A, fast enough for short circuits in residential or light commercial final circuits with resistive or modest inductive loads.
Deployment context
Clip-on DIN rail mount, 36 mm (4 x 9 mm pitches). Fits standard modular enclosures.
Current production per the manufacturer's lifecycle status.