Schneider Electric A9DGB632 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9DGB632 Acti9 iCV40 RCBO, 32 A, 30 mA, B

MPNA9DGB632
Active

Schneider Electric Acti9 iCV40 RCBO, A9DGB632, 1P+N, 32 A, B curve, 100 mA sensitivity, 6 kA Icn, clip-on DIN rail.

$230.63Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9DGB632 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)100 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication Fault indication
A9DGB632 — Electrical Ratings
ParameterValue
Rated current (In)32 A
Rated operational voltage (Ue)230 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9DGB632 — Identification
ParameterValue
Product nameActi9 iCV40
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiCV40N
A9DGB632 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height94 mm
Depth74 mm
A9DGB632 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Operating altitude2000 m
A9DGB632 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The Schneider Electric A9DGB632 is an Acti9 iCV40 residual current circuit breaker with overcurrent protection (RCBO) rated at 32 A, B curve, with integrated 100 mA earth-leakage protection.

The 100 mA sensitivity is higher than the 30 mA typically specified for personal shock protection; it is selected where nuisance tripping from leakage in long cable runs or equipment with natural leakage (heaters, motors with filters) would otherwise cause unwanted downtime. The thermal-magnetic trip unit provides inverse-time overload protection and instantaneous short-circuit response in one package.

Neutral is on the left (1P+N configuration). Tunnel terminals accept 1–16 mm² rigid or 1–10 mm² flexible cable; tighten to 2 N·m. The 9 mm phase-to-neutral pitch matches the Acti9 busbar system for daisy-chaining outgoing circuits in a distribution board.

Frequently asked questions

What are the key ratings of A9DGB632?

Rated current 32 A, B curve, 100 mA earth-leakage sensitivity, 6 kA breaking capacity at 230 V AC, 1P+N poles, thermal-magnetic trip, limitation class 3.

Where can I buy A9DGB632?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What compliance documentation does Schneider provide for A9DGB632?

The A9DGB632 carries EAC and VDE quality labels and is designed to EN/IEC 61009-2-1. Standard compliance documentation (declaration of conformity, CE marking) is available from Schneider Electric.

MPN
A9DGB632