Skip to main content
Schneider Electric A9F03163 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F03163 Acti9 iC60N MCB, 63 A, 1P, B-Cur

MPNA9F03163
Active

Schneider Electric Acti9 iC60N, A9F03163, miniature circuit breaker, 1P, 63 A, B-curve, 36 kA breaking capacity, DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F03163 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameIC60N
Poles description1P
Number of protected poles1
Device applicationDistribution
A9F03163 — Electrical & Protection
ParameterValue
Rated current (In)63 A
Tripping curve codeB
Magnetic tripping limit4 x In +/- 20 %
Breaking capacity (Icu / AIR)36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9F03163 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Mounting supportDIN rail
Width18 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)3.5 N.m top or bottom
A9F03163 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9F03163 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1
A9F03163 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

It's built for distribution panels and final-subcircuit protection, switching both AC and DC networks at 50/60 Hz. Rated 36 kA Icu at 12…60 V AC and 15 kA Icu at 12…60 V DC per EN/IEC 60947-2, with a 6 kA Icn at 230 V AC per EN/IEC 60898-1. That dual-rating means it's suitable for both industrial panel feeders (60947-2) and standard household-style branch circuits (60898-1) — a common spec for commercial distribution gear. The B-curve magnetic trip triggers at 4 x In ±20 %, so it clears fast on short-circuit but tolerates modest inrush — typical for resistive or general-purpose loads where you don't need the delay of a C-curve.

Snaps onto DIN rail, 18 mm per pole (2 x 9 mm pitches). The 1P body is 78.5 mm deep and 91 mm tall — standard compact MCB footprint that fits existing distribution boards without re-spacing.

Current production item in the Acti9 range.

Frequently asked questions

What compliance standards does A9F03163 meet?

Certified to EN/IEC 60947-2 and EN/IEC 60898-1. It also carries tropicalisation class 2 per IEC 60068-1, pollution degree 3, and overvoltage category IV.

MPN
A9F03163