The A9F03206 is a 2-pole miniature circuit-breaker from the Acti9 iC60N family, rated 6 A with a B-curve trip characteristic (magnetic trip at 4 x In ±20 %). The 36 kA Icu at 12–133 V AC (EN/IEC 60947-2) tells you it can safely interrupt a fault up to that level without welding contacts or cascading upstream; at 220–240 V AC that drops to 20 kA Icu, and at 380–415 V AC to 10 kA Icu. Dual-certified to both standards means it can be specified in industrial panels (60947-2) or final-distribution boards (60898-1) — the same part, different paperwork.
Deployment context
IP20 finger-safe front; the terminals accept up to 25 mm² rigid or 16 mm² flexible, with a 14 mm strip length and 2 N·m torque.
Pollution degree 3 (conforms to 60947-2) rates it for conductive environments — typical in control panels. Overvoltage category IV, so it can be installed at the service entrance. No separate RoHS/REACH statement in the evidence, but Schneider Electric standard compliance documentation is available on request with the RFQ.