Skip to main content
Schneider Electric A9F03310 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F03310 Acti9 iC60N MCB, B-Curve 10 A 3P

MPNA9F03310
Active

Schneider Electric Acti9 iC60N, miniature circuit breaker, A9F03310, B-curve, 10 A rated current, 3 poles, breaking capacity 36 kA Icu at 12...133 V AC, DIN rail mount, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F03310 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9F03310 — Ratings
ParameterValue
Rated current (In)10 A
Poles configuration3P
Number of protected poles3
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV
A9F03310 — Protection
ParameterValue
Curve codeB
Trip unit technologyThermal-magnetic
Magnetic tripping limit4 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles
A9F03310 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6
A9F03310 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9F03310 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F03310 is a 3-pole miniature circuit breaker from the Acti9 iC60N range, rated 10 A with a B-curve trip characteristic. The 36 kA Icu at 12…133 V AC (per EN/IEC 60947-2) tells you it can safely interrupt a fault current up to 36 kA at those low voltages; at 220…240 V AC the rating drops to 20 kA, and at 380…415 V AC to 10 kA. The part also carries a 6 kA Icn at 400 V per EN/IEC 60898-1, which is the standard household/commercial breaking capacity for that standard.

The 78.5 mm depth and 91 mm height are standard for the iC60N family, so it aligns with busbars and neighbouring devices in an Acti9 distribution board. Terminals accept 1…25 mm² rigid or 1…16 mm² flexible wire; strip length is 14 mm, torque to 2 N·m.

The thermal-magnetic trip unit provides both overload (thermal) and short-circuit (magnetic) protection. A separate earth-leakage protection block can be added if needed.

Frequently asked questions

How do I get current pricing and availability for A9F03310?

Pricing and availability are confirmed at quote time against an RFQ through independent distribution channels. Submit an RFQ for a current quote.

What is A9F03310's breaking capacity at 400 V?

At 400 V AC 50/60 Hz, the A9F03310 has a breaking capacity of 10 kA Icu per EN/IEC 60947-2 and 6 kA Icn per EN/IEC 60898-1.

What compliance documentation does this brand provide for A9F03310?

The part is certified to EN/IEC 60947-2 and EN/IEC 60898-1. It carries tropicalisation class 2 per IEC 60068-1 and is rated for pollution degree 3 and overvoltage category IV.

MPN
A9F03310