Schneider Electric A9F03325 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F03325 Acti9 iC60N MCB, 25 A, 3P, Curve

MPNA9F03325
Active

Schneider Electric Acti9 iC60N, A9F03325, miniature circuit breaker, 25 A, 3P, curve B, 36 kA Icu at 12-133 V AC, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F03325 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9F03325 — Ratings
ParameterValue
Rated current (In)25 A
Poles configuration3P
Number of protected poles3
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV
A9F03325 — Protection
ParameterValue
Curve codeB
Trip unit technologyThermal-magnetic
Magnetic tripping limit4 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles
A9F03325 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6
A9F03325 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9F03325 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F03325 is an Acti9 iC60N miniature circuit breaker, 25 A rated current, 3-pole, curve B. That curve B magnetic trip (4 x In ±20%) means it's sized for resistive or lighting loads where inrush is low — not motor starting or transformer primaries that'd nuisance-trip on a B curve. The 36 kA Icu at 12-133 V AC (EN/IEC 60947-2) gives it serious fault-clearing headroom on low-voltage distribution; at 220-240 V it still holds 20 kA. Dual-rated to both EN/IEC 60898-1 and EN/IEC 60947-2, so it qualifies for both domestic-panel and industrial panelboard specs.

Snaps onto DIN rail (mounting support: DIN rail,). Three-pole, 54 mm wide — that's 6 x 9 mm pitches, so it fills six module positions on the rail. IP20 finger-safe front, pollution degree 3, overvoltage category IV — panel builders can land this in a main distribution board without derating for contamination.

Frequently asked questions

What are the key ratings for the A9F03325?

25 A rated current, 3-pole, curve B magnetic trip (4 x In ±20%). Breaking capacity: 36 kA Icu at 12-133 V AC, 20 kA at 220-240 V AC, 10 kA at 380-415 V AC, 6 kA at 440 V AC per EN/IEC 60947-2; also rated 10 kA Icn at 400 V per EN/IEC 60898-1. Dual-standard certified to both EN/IEC 60947-2 and EN/IEC 60898-1.