Skip to main content
Schneider Electric A9F03425 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F03425 Acti9 iC60N MCB, 25 A, 4P, B-Cur

MPNA9F03425
Active

Schneider Electric Acti9 iC60N, miniature circuit-breaker, 4P, 25 A, B-curve, 36 kA Icu at 12...133 V AC, DIN rail mount, white.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F03425 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9F03425 — Ratings
ParameterValue
Rated current (In)25 A
Poles configuration4P
Number of protected poles4
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV
A9F03425 — Protection
ParameterValue
Curve codeB
Trip unit technologyThermal-magnetic
Magnetic tripping limit4 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles
A9F03425 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8
A9F03425 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9F03425 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The A9F03425 is a Schneider Electric Acti9 iC60N miniature circuit-breaker rated 25 A with a B-curve magnetic trip (4 x In ±20 %), meaning it trips instantaneously between 80 A and 120 A — right-sized for resistive or general-purpose loads where you want fast fault clearing without nuisance trips from inrush. The 4-pole (4P) construction isolates all phases and neutral in a single module, saving DIN-rail space compared to separate breakers. Breaking capacity hits 36 kA Icu at 12–133 V AC and still holds 10 kA Icu at 380–415 V AC, so it handles high-fault panels without cascading upstream. Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (residential/commercial), which means it qualifies for both distribution boards and industrial control panels — one part number for mixed environments.

Snaps onto standard DIN rail — 9 mm pitch, 8 modules wide (72 mm). The double terminals accept 1–25 mm² rigid or 1–16 mm² flexible on top or bottom, with a 14 mm strip length and 2 N·m tightening torque. IP20 finger-safe terminals keep live parts covered during commissioning. Overvoltage category IV means it can be installed at the service entrance, not just downstream sub-panels.

Durability and environmental specs

Rated for 10,000 electrical cycles and 20,000 mechanical cycles — enough for frequent switching in lighting or motor control circuits. The thermal-magnetic trip unit provides both overload protection (thermal bimetal) and short-circuit protection (magnetic solenoid) in one compact package. Earth-leakage protection requires a separate Vigi block, not built in.

Frequently asked questions

What is the breaking capacity of A9F03425 at 400 V?

At 380–415 V AC, the A9F03425 delivers 10 kA Icu per EN/IEC 60947-2, and 6 kA Icn at 400 V per EN/IEC 60898-1. The 36 kA Icu rating applies at 12–133 V AC.

Where can I buy A9F03425 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ with your target quantity; we'll confirm availability and current pricing at quote time.

What standards does A9F03425 comply with?

Dual-certified to EN/IEC 60947-2 (industrial circuit-breaker standard) and EN/IEC 60898-1 (residential/commercial MCB standard). Also carries suitability for isolation per both standards.

What is the closest alternative to A9F03425 in the Acti9 family?

The A9F03425 is the 25 A, 4P, B-curve variant. The C-curve sibling (A9F04425) has a magnetic trip at 5–10 x In instead of 3–5 x In, making it better for motor or transformer loads with higher inrush. If you need a different current rating, the iC60N range covers 1 A to 63 A in the same footprint.

MPN
A9F03425