Skip to main content
Schneider Electric A9F03613 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F03613 Acti9 iC60N MCB, 13 A, 1P+N, B-C

MPNA9F03613
Active

Schneider Electric Acti9 iC60N, A9F03613, miniature circuit breaker, 13 A, 1P+N, B-curve, 36 kA Icu at 12-60 V AC, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F03613 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameIC60N
Poles description1P + N
Number of protected poles1
Device applicationDistribution
A9F03613 — Electrical & Protection
ParameterValue
Rated current (In)13 A
Tripping curve codeB
Magnetic tripping limit4 x In +/- 20 %
Breaking capacity (Icu / AIR)36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9F03613 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Width36 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom
A9F03613 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9F03613 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1
A9F03613 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The A9F03613 is a 13 A, 1P+N miniature circuit breaker from the Schneider Acti9 iC60N family. The B-curve (magnetic tripping limit 4 x In +/-20%) means it trips instantaneously between 3.2 and 5.2 times rated current — suited for resistive and general-purpose loads where inrush is moderate, like lighting or small control transformers. The 36 kA Icu at 12-60 V AC (EN/IEC 60947-2) is the interrupting capacity under short-circuit conditions; at 230 V AC the Icn is 6000 A per EN/IEC 60898-1. Dual-rated to both standards, so it covers both distribution (60947-2) and household/commercial (60898-1) applications. The 1P+N configuration switches the line pole and provides a switched neutral — common in single-phase final circuits where neutral isolation is required.

Snaps onto DIN rail (mounting support: DIN rail). Depth is 78.5 mm, height 91 mm. Terminals accept 1-25 mm² rigid or 1-16 mm² flexible; double terminal top or bottom allows daisy-chaining or feed-through. Tightening torque 2 N.m. Wire stripping length 14 mm. IP20 finger-safe terminals. Pollution degree 3 (industrial environment).

Frequently asked questions

What is the breaking capacity of A9F03613?

36 kA Icu at 12-60 V AC (EN/IEC 60947-2), 20 kA Icu at 100-133 V AC, 10 kA Icu at 220-240 V AC, and 6000 A Icn at 230 V AC (EN/IEC 60898-1).

What is A9F03613's listed depth?

78.5 mm.

What compliance documentation does Schneider provide for A9F03613?

The breaker is dual-rated to EN/IEC 60947-2 and EN/IEC 60898-1, carries IP20 protection, and is tropicalised per IEC 60068-1 (2 levels).

Where can I buy A9F03613?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

MPN
A9F03613