Skip to main content
Schneider Electric A9F03616 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F03616 Acti9 iC60N MCB, B Curve 16 A 1P

MPNA9F03616
Active

Schneider Electric Acti9 iC60N, A9F03616, miniature circuit breaker, B curve, 16 A, 1P+N, 36 kA breaking capacity, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F03616 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameIC60N
Poles description1P + N
Number of protected poles1
Device applicationDistribution
A9F03616 — Electrical & Protection
ParameterValue
Rated current (In)16 A
Tripping curve codeB
Magnetic tripping limit4 x In +/- 20 %
Breaking capacity (Icu / AIR)36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9F03616 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Width36 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom
A9F03616 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9F03616 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1
A9F03616 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The A9F03616 is a Schneider Electric Acti9 iC60N miniature circuit breaker (MCB) rated 16 A with a B curve, meaning its magnetic trip threshold is 4 x In ±20% — it clears short-circuit faults between 64 A and 80 A. The 1P+N configuration protects one pole and switches the neutral, so it fits single-phase distribution boards where neutral isolation is needed without overcurrent protection on the neutral. Breaking capacity is the headline: 36 kA Icu at 12…60 V AC, 20 kA at 100…133 V, and 10 kA at 220…240 V per EN/IEC 60947-2, plus 6000 A Icn at 230 V per EN/IEC 60898-1. Dual certification to both the industrial (60947-2) and residential (60898-1) standards means this MCB qualifies for either duty class.

Snaps onto standard DIN rail. Width is 36 mm (4 x 9 mm pitches), height 91 mm, depth 78.5 mm. The toggle actuator and trip indicator are front-facing; neutral position is left. Terminals accept 1…25 mm² rigid or 1…16 mm² flexible wire, with a tightening torque of 2 N.m. IP20 finger-safe protection means it belongs inside a closed panel, not exposed to washdown.

Frequently asked questions

Where can I buy A9F03616 and get a price?

The A9F03616 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of A9F03616 at 240 V?

At 220…240 V AC per EN/IEC 60947-2 the breaking capacity is 10 kA Icu; at 230 V per EN/IEC 60898-1 it is 6000 A Icn.

What standards does A9F03616 comply with?

It is dual certified to EN/IEC 60947-2 (industrial MCB standard) and EN/IEC 60898-1 (residential / commercial MCB standard). It also meets isolation requirements per both standards.

MPN
A9F03616