Skip to main content
Schneider Electric A9F03716 — Miniature Circuit Breakers (MCB)

A9F03716 Acti9 iC60N MCB, 16 A, Curve B, 3P+N

MPNA9F03716
Active

Schneider Electric Acti9 iC60N miniature circuit-breaker, A9F03716, 16 A rated, curve B, 3P+N, 36 kA breaking capacity at 133 V AC, DIN rail mount, thermal-magnetic trip.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F03716 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9F03716 — Ratings
ParameterValue
Rated current (In)16 A
Poles configuration3P + N
Number of protected poles3
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV
A9F03716 — Protection
ParameterValue
Curve codeB
Trip unit technologyThermal-magnetic
Magnetic tripping limit4 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles
A9F03716 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8
A9F03716 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9F03716 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F03716 is an Acti9 iC60N miniature circuit-breaker (MCB) rated at 16 A, curve B, in a 3P+N (three-pole plus neutral) format. It is a thermal-magnetic trip device designed for distribution circuits in commercial and industrial panels. Its breaking capacity spans 36 kA Icu at 12–133 V AC, 20 kA at 220–240 V AC, 10 kA at 380–415 V AC, and 6 kA at 440 V AC per EN/IEC 60947-2, plus a 6000 A Icn at 400 V AC per EN/IEC 60898-1. That dual rating means it qualifies for both industrial (60947-2) and residential/commercial (60898-1) applications — a single part number covers both compliance paths.

The 3P+N format places the neutral pole on the left, with the three phase poles to its right. Double terminals top and bottom accept 1–25 mm² rigid or 1–16 mm² flexible cable; torque to 2 N·m. IP20 rated, so it belongs inside an enclosure — not exposed to washdown or outdoor weather.

Frequently asked questions

What is the breaking capacity of A9F03716 at 400 V?

At 400 V AC the A9F03716 delivers 10 kA Icu per EN/IEC 60947-2 and 6000 A Icn per EN/IEC 60898-1.

Where can I buy A9F03716 and what is the lead time?

The A9F03716 is available to order through independent distribution. Submit an RFQ for current availability and pricing — lead time and stock are confirmed at quote time.

What standards does the A9F03716 comply with?

It is dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (residential/commercial), with suitability for isolation per both standards.

What is the depth of A9F03716?

The depth is 78.5 mm, with a height of 91 mm and width of 72 mm (8 x 9 mm pitches).

MPN