Skip to main content
Schneider Electric A9F03750 — Miniature Circuit Breakers (MCB)

A9F03750 Acti9 iC60N MCB, 50 A, 3P+N, B Curve, 36 kA

MPNA9F03750
Active

Schneider Electric Acti9 iC60N miniature circuit breaker, A9F03750, 50 A, 3P+N, B curve, 36 kA Icu at 133 V AC, dual standard EN/IEC 60947-2 and 60898-1, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F03750 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9F03750 — Ratings
ParameterValue
Rated current (In)50 A
Poles configuration3P + N
Number of protected poles3
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV
A9F03750 — Protection
ParameterValue
Curve codeB
Trip unit technologyThermal-magnetic
Magnetic tripping limit4 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles
A9F03750 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8
A9F03750 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9F03750 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

Acti9 iC60N A9F03750 — 50 A, 3P+N, B Curve MCB

The Schneider Electric A9F03750 is an Acti9 iC60N miniature circuit breaker rated at 50 A, 3P+N poles, with a B tripping curve. The 3P+N configuration switches all three phases and provides a switched neutral on the left pole, per the neutral position spec. Breaking capacity is dual-rated: 36 kA Icu at 12–133 V AC, 20 kA at 220–240 V, 10 kA at 380–415 V, and 6 kA at 440 V per EN/IEC 60947-2, plus 6 kA Icn at 400 V per EN/IEC 60898-1. The higher Icu figures under 240 V mean this breaker handles substantial fault current on low-voltage secondary side of a transformer or in a sub-distribution board. The dual standard certification (60947-2 for industrial and 60898-1 for residential/commercial) gives flexibility for BOM consolidation across different installation types.

DIN Rail Integration and Panel Fit

Mounts on standard DIN rail per the mounting support spec. Width is 72 mm (8 x 9 mm pitches), height 91 mm, depth 78.5 mm. The double terminal accepts 1–35 mm² rigid or 1–25 mm² flexible wire; strip length is 14 mm. IP20 rated, so it belongs inside a panel enclosure, not exposed to washdown.

Suitability for isolation is confirmed under both standards. Overvoltage category IV — suitable for main distribution board installation.

Frequently asked questions

How do I get current pricing and availability for A9F03750?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is A9F03750's breaking capacity at 400 V?

At 400 V AC 50/60 Hz, the Icn rating per EN/IEC 60898-1 is 6000 A, and the Icu per EN/IEC 60947-2 is 10 kA at 380–415 V.

What wire sizes does the A9F03750 terminal accept?

The double terminal accepts 1–35 mm² rigid or 1–25 mm² flexible wire, with a strip length of 14 mm and tightening torque of 3.5 N.m.

MPN