Skip to main content
Schneider Electric A9F04132 — 1-Pole MCB (DIN Rail)

A9F04132 Acti9 iC60N MCB, 32 A, 1P, C-Curve, 36 kA

MPNA9F04132
Active

Schneider Electric Acti9 iC60N miniature circuit breaker, A9F04132, 1-pole, 32 A rated current, C-curve, 36 kA Icu breaking capacity at 12-60 V AC, DIN-rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F04132 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameIC60N
Poles description1P
Number of protected poles1
Device applicationDistribution
A9F04132 — Electrical & Protection
ParameterValue
Rated current (In)32 A
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu / AIR)36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9F04132 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Mounting supportDIN rail
Width18 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)3.5 N.m top or bottom
A9F04132 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9F04132 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1
A9F04132 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The Schneider Electric A9F04132 is a 1-pole Acti9 iC60N miniature circuit breaker rated 32 A with a C-curve magnetic trip (8 x In ±20 %). The dual certification to both EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (domestic/residential) gives it a wider application envelope than a standard domestic MCB; the 60947-2 rating is the one to use for industrial panel SCCR calculations. The thermal-magnetic trip unit handles overloads (thermal bimetal) and short-circuits (magnetic coil) in one compact 18 mm wide package — two 9 mm pitches on the DIN rail. The IP20 finger-safe terminals accept up to 35 mm² rigid or 25 mm² flexible conductors, with a 3.5 N.m tightening torque and 14 mm strip length.

The 78.5 mm depth and 91 mm height fit standard distribution boards and small enclosures without crowding the gland plate. Toggle control with a visible trip indicator and contact position indicator means a quick visual check from the cabinet door confirms the breaker state without opening the cover.

Frequently asked questions

What is the breaking capacity of A9F04132 at 230 V AC?

At 220-240 V AC 50/60 Hz the A9F04132 has a 10 kA Icu per EN/IEC 60947-2 and a 6 kA Icn at 230 V AC per EN/IEC 60898-1. The 36 kA Icu rating applies at 12-60 V AC.

What is the closest alternative to A9F04132 in the same family?

Within the Acti9 iC60N range, the closest sibling is the same 1-pole C-curve breaker at a different current rating — for example the A9F04131 (25 A) or A9F04133 (40 A). The physical footprint, breaking capacity, and terminal specs are identical; only the thermal trip threshold changes. No pin-compatible alternative exists outside the Acti9 iC60 family without verifying the DIN-rail pitch and terminal layout.

What compliance documentation does Schneider provide for A9F04132?

The A9F04132 carries dual certification to EN/IEC 60947-2 and EN/IEC 60898-1, with IP20 finger protection per IEC 60529 and tropicalisation class 2 per IEC 60068-1. Standard Schneider documentation includes the declaration of conformity (CE/UKCA), RoHS and REACH compliance statements, and the product datasheet with detailed breaking capacity tables.

Where can I buy A9F04132 and how is it quoted?

The A9F04132 is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time for your quantity.

MPN
A9F04132