Skip to main content
Schneider Electric A9F04301 — Miniature Circuit Breakers (MCB)

A9F04301 Acti9 iC60 Miniature Circuit-Breaker, 1 A, C Curve,

MPNA9F04301
Active

Schneider Electric Acti9 iC60 miniature circuit-breaker, A9F04301, 1 A rated current, C curve, 3 poles, 50 kA Icu at 415 V AC, DIN rail mount, white.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F04301 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F04301 — Ratings
ParameterValue
Rated current (In)1 A
Poles configuration3P
Number of protected poles3
Breaking capacity50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F04301 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F04301 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6

Environmental

A9F04301 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F04301 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The A9F04301 is a Schneider Electric Acti9 iC60 miniature circuit-breaker rated at 1 A with a C curve, three poles, and a breaking capacity of 50 kA Icu at 415 V AC. It's a thermal-magnetic trip unit designed for distribution circuits on DIN rail, covering both AC and DC networks at 50/60 Hz.

The 1 A rating with C curve (magnetic trip at 8 x In ±20%) means this breaker protects small loads like control transformers or signal circuits where inrush is moderate — not motor feeders. The 10 kA Icn at 400 V (per EN/IEC 60898-1) is the domestic/commercial rating — the higher Icu figure is the industrial one that matters for distribution boards with large upstream transformers. The IP20 finger-safe terminals are standard for enclosed gear; no washdown rating here.

Snaps onto DIN rail, 54 mm wide (6 x 9 mm pitches), 91 mm tall, 78.5 mm deep. Double terminals top and bottom accept 1–25 mm² rigid or 1–16 mm² flexible — strip 14 mm, torque to 2 N.m. The toggle handle and trip indicator give local status; a separate earth-leakage block can be added alongside.

Frequently asked questions

Where can I buy A9F04301 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for current pricing and availability.

What is A9F04301's breaking capacity at 415 V AC?

It carries 50 kA Icu at 380–415 V AC per EN/IEC 60947-2, and 10 kA Icn at 400 V per EN/IEC 60898-1.

What compliance standards does A9F04301 meet?

It conforms to EN/IEC 60947-2 and EN/IEC 60898-1, with tropicalisation class 2 per IEC 60068-1 and suitability for isolation per both standards.

MPN
A9F04301